Filter Fan Plus
FPI/FPO 018 | 11.46 x 11.46" (up to 606.8 cfm)

  • New air-flap outlet technology for high airflow
  • Easy mounting
  • Protection type/Environmental ratings by independent testing agencies (VDE & UL)
  • Two optional systems for optimal airflow (FPI/FPO)
  • Industry-common enclosure cut-out sizes (5 sizes)
  • Single filter mat system design
  • Two fan speeds

Filter fans are used to provide "cooling" by forced air-circulation in enclosures and cabinets containing electrical/electronic and other components. The interior temperature of an enclosure can be reduced by channeling cooler, filtered outside air into the enclosure, thus expelling hot inside air. The resulting airflow prevents formation of localized hot pockets and protects electronic components from overheating.

The Filter Fan Plus series encompasses a new air-flap technology on the air outlet side, thereby reaching an unparalleled high degree of airflow. A unique ratchet mechanism is used for easy installation. It provides safe and secure mounting while guaranteeing a tight seal. Depending on the requirements, there are two optional systems available – the FPI or the FPO system (FPI = "in", FPO = "out"). The FPI system is the more commonly known installation system, where a filter fan located in the lower part of the enclosure draws cleaner, cooler air into the enclosure (airflow direction "In"). This system consists of a filter fan and exhaust filter. On opposite, with the newer FPO system, the filter fan will be located in the upper area of the enclosure to draw warmer air out of the enclosure (airflow direction "Out"). The FPO system consists of an intake filter and exhaust filter fan. The Filter Fan Plus series may also be used outdoors with appropriate protective measures or when equipped with weather proof accessories, e.g. Hose-proof Hood FFH 086.

Axial fan, ball bearingfan speed 1: service life L10 at +104 °F (+40 °C): min. 76,000 h
metal impeller
fan speed 2: service life L10 at +104 °F (+40 °C): min. 54,000 h
plastic impeller
Connection3-pole clamp for AWG 14 (2.5 mm²), clamping torque 0.8 Nm max.
Housing, hood, flapsplastic UL 94V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out11.5 x 11.5+0.04 inches (291 x 291+1 mm)
Mounting frame4 built-in ratchet push levers for mounting
(6 ratchet stops to accommodate for wall
thicknesses Gauge 9 to 19 or 1-4 mm).
Additional screw mounting possible if needed1.
Filter matG3 acc. to DIN EN 779, average arrestance Aa 84 %
Filter materialsynthetic mesh with progressive construction, temperature
resistant to 212 °F (100 °C), self-extinguishing class F1,
moisture resistant to 100 % RH, reusable
Operating temperaturefan speed 1 & 2, 50 Hz: -13 to +131 °F (-25 to +55 °C)
fan speed 1, 60 Hz: -13 to +95 °F (-25 to +35 °C)
fan speed 2, 60 Hz: -13 to +122 °F (-25 to +50 °C)
Storage temperature-40 to +158 °F (-40 to +70 °C)
Operating/Storage humiditymax. 75 % RH (non-condensing)
Protection type/Protection classIP54 / I (grounded)
Environmental rating UL/NEMAUL TYPE 12 / NEMA 12
ApprovalsVDE, UL File No. E234324, EAC
Noteother voltages on request

1 Drilling hole markings for screw mounting are indicated on mounting frame.

Airflow direction "In": Filter Fan FPI 018

Part No.Operating voltageFan speedAir volume,
free blowing
Air volume
with exhaust filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Mounting depthWeight
(approx.)
Filter mat
01874.0-30AC 230 V, 50/60 Hz   1254.8 cfm
(433 m³/h)
219.5 cfm
(373 m³/h)
400/480 mA95 W62 dB (A)6.3"
(160 mm)
6.8 lbs.
(3.1 kg)
G3
01874.0-31AC 230 V, 50/60 Hz   2367.3 cfm
(624 m³/h)
329.6 cfm
(560 m³/h)
550/700 mA140 W70 dB (A)6.3"
(160 mm)
7.3 lbs.
(3.3 kg)
G3
01874.9-30AC 115 V, 50/60 Hz   1231.9 cfm
(394 m³/h)
199.5 cfm
(339 m³/h)
660/800 mA90 W61 dB (A)6.3"
(160 mm)
6.8 lbs.
(3.1 kg)
G3
01874.9-31AC 115 V, 50/60 Hz   2391.4 cfm
(665 m³/h)
349 cfm
(593 m³/h)
1100/1450 mA165 W72 dB (A)6.3"
(160 mm)
7.3 lbs.
(3.3 kg)
G3

Airflow direction "In": Exhaust Filter FPI 118

Part No.Mounting depthWeight (approx.)Air outlet
11874.0-002.0" (50 mm)2.2 lbs. (1.0 kg)air-flap outlet technology

To top

Airflow direction "Out": Filter Fan FPO 018

Part No.Operating
voltage
Fan speedAir volume,
free blowing
Air volume
with intake filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Mounting
depth
Weight
(approx.)
Air outlet
01884.0-00AC 230 V,
50/60 Hz
   1427.9 cfm
(727 m³/h)
243.1 cfm
(413 m³/h)
400/480 mA95 W63 dB (A)6.3"
(160 mm)
7.0 lbs.
(3.2 kg)
air-flaps
01884.0-01AC 230 V,
50/60 Hz
   2594.5 cfm
(1010 m³/h)
352.6 cfm
(599 m³/h)
550/700 mA140 W70 db (A)6.3"
(160 mm)
7.5 lbs.
(3.4 kg)
air-flaps
01884.9-00AC 115 V,
50/60 Hz
   1413.8 cfm
(703 m³/h)
230.1 cfm
(391 m³/h)
660/800 mA90 W62 dB (A)6.3"
(160 mm)
7.0 lbs.
(3.2 kg)
air-flaps
01884.9-01AC 115 V,
50/60 Hz
   2606.8 cfm
(1031 m³/h)
358.4 cfm
(609 m³/h)
1100/1450 mA165 W71 db (A)6.3"
(160 mm)
7.5 lbs.
(3.4 kg)
air-flaps

Airflow direction "Out": Intake Filter FPO 118

Part No.Mounting depthWeight (approx.)Filter mat
11884.0-301.0" (25 mm)

1.8 lbs. (0.8 kg)

ISO coarse 55% acc. to ISO 16890 (G3), initial gravimetric arrestance 57%

Filter Mat FM 086

Filter class11.14 x 11.14" (283 x 283 mm)Initial gravimetric arrestance 1 packing unit
ISO coarse 55% acc. to ISO 16890 (G3)Part No. 08637.0-0057 %5 pieces

To top

Dimensioned Drawing

FPI 018/FPI 118
FPO 018/FPO 118