- Analog/digital interface
- Small size
- Easy DIN rail and/or screw mount
- High accuracy
- Quick connection (M12 plug-in connector)
- Large temperature and humidity range
- Various application areas (IEC 61010-1/DIN EN 61010-1)
The compact Smart Sensor CSS 014 electronically records temperature and humidity and converts the measured data into a standardized analog 4-20 mA or a digital IO-Link signal. The converted value signals can be utilized or further processed by a control or monitoring unit, e.g. a PLC control. The Smart Sensor is suitable for installation inside and outside the enclosure, even in harsh environmental conditions as can be found in the wind power industry: in shielded outdoor areas and exposed to vibrations.
Technical Data
Download IO-Link Parameter Leaflet for Smart Sensor with IO-Link Interface
Download IODD for Smart Sensor CSS 014 with IO-Link Interface
Download IODD and all accompanying files, then import IODD file into your control software. Or go to the official IODDfinder by IO-Link.
DOWNLOAD OPERATING INSTRUCTIONS CSS 014 Analog
DOWNLOAD OPERATING INSTRUCTIONS CSS 014 IO-Link
Measuring signals analog (4-20 mA)/digital (IO-Link) digital (IO-Link) | temperature, humidity events, diagnosis, device data |
---|---|
Max. reaction time | 3 min. |
Load resistance (external) | ≤ 500 Ω (4-20 mA only) |
Connection | M12 round plug connector, IEC 61076-2-101, 4-pin, A-coded, shielded |
Electrical protection | Reverse-polarity, short circuit, overvoltage protection |
Mounting | clip for 35 mm DIN rail, EN 60715 or M5 screws (not included) |
Housing | plastic, UL94 V-0, light grey |
Dimensions | 5.5 x 1.6 x 1.5" (140 x 40 x 38 mm) |
Weight | approx. 1.8 oz. (50 g) |
Mounting position | vertical (connection on top) |
Storage temperature | -40 to +185 °F (-40 to +85 °C) |
Operating/Storage humidity | max. 90% RH (non-condensing) |
Protection type1/Protection class | IP20 (sensor only: IP57) / III (SELV) |
Approvals | UL File No. E500143, VDE (acc. to IEC 61010-1/DIN EN 61010-1), EAC |
Note | Other measuring ranges available upon request |
¹ The PCB (printed circuit board) is coated on both sides with a certified protective lacquer to protect against corrosion and for improvement of the tracking resistance.
Part No. | Interface | Operating voltage | Power consumption max. | Temperature measuring range | Humidity measuring range | Operating temperature | |
---|---|---|---|---|---|---|---|
01420.2-00 | 4-20 mA (analog) | DC 24 V (DC 12-30 V) | 1.8 W (typically 0.4 W) | -40 to +140 °F (40 to +60 °C) ± 1 K | 0 to 100 % RH ± 4%2 | -40 to +158 °F (-40 to +70 °C) | |
01411.2-00 | IO-Link (digital, specified acc. to version 1.1) | DC 24 V (DC 18-30 V) | 0.3 W | -40 to +176 °F (-40 to +80 °C) ± 0.3 K | 0 to 100% RH ± 3%2 | -40 to +176 °F | |
2 Tolerance within 20 to 80 % RH (please request diagram for tolerances outside this range)