Switch Module (Relay)
DCM 010 | DC 20 to 56 V

  • High DC switching capacity
  • Variety of applications
  • Wide DC voltage range
  • Simple connection

The DCM 010 is used to control DC powered devices with high capacities in control and switch cabinets. It is controlled via an external potential-free contact (thermostat or hygrostat), which is connected between terminal 3 and 4. It must be ensured that the external contact is suitable to switch the required signal current without any problems.

Contact typeNO - normally open (MOSFET)
Service life> 100,000 cycles
Operating voltageDC 20 to 56 V
Control contact – signal current3 mA at DC 20 V / 4.5 mA at DC 24 V
14 mA at DC 48 V / 17 mA at DC 56 V
Connection6-pole terminal: stranded wire1 AWG 16 (1.5 mm²);
max. AWG 12 (2.5 mm²)
Mountingclip for 35mm DIN rail, EN 60715
Housingplastic, UL 94V-0, grey (bicolor)
Dimensions3.7 x 2.1 x 1.7" (93 x 53 x 44 mm)
Weightapprox. 2.3 oz. (65 g)
Mounting positionvertical
Operating temperaturesee article table below
Storage temperature-40 to +176 °F (-40 to +80 °C)
Operating/Storage humiditymax. 90 % RH (non-condensing)
Protection typeIP20
ApprovalsUL File No. E342261, VDE, EAC
Noteother versions on request

1 When connecting with stranded wires, wire end ferrules must be used.

Part No.Max. switching capacity
(relay output)
Operating temperature
01010.0-00DC 15 A-40 °F to +104 °F (-30 °C to +40 °C)
01010.0-10DC 13 A-22 °F to +122 °F (-30 °C to +50 °C)
01010.0-20DC 11 A-22 °F to +140 °F (-30 °C to +60 °C)

Dimensioned Drawing

Switch Module (Relay) DCM 010 (DC 20 to 56 V)