- Large setting range
- Compact design
- Small hysteresis
- Optical function display
- Signal application
The electronic thermostat is used for controlling heating and cooling equipment, filter fans or signal devices through the Relay DCM 010 or a similar device. The thermostat registers the surrounding air temperature and can switch a signal current via an internal relay with a potential free change-over contact. The LED integrated in the adjustment knob shows the closed status of the contact 1-2. When the temperature rises contact 1-2 opens and the LED turns off. In currentless state (no supply voltage) contact 1-2 opens.
Switching difference | 7 °F (4 K) ± 1.8 °F (1 K) tolerance at +68 °F (+20 °C) |
---|---|
Sensor element | NTC |
Reaction time | approx. 5 sec. |
Contact type | SPDT / change-over |
Service life | >100,000 cycles (at 10 mW) |
Max. switching capacity (relay output) | 0.5 A at DC 48 V |
Min. switching load | DC 10 mW (at 0.1 V, 100 mA or 1 mA, 10 V) |
Optical indicator | LED |
Connection | 5-pole terminal, clamping torque 0.5 Nm max.: |
Housing | plastic, UL 94V-0, light grey |
Mounting | clip for 35 mm DIN rail, EN 60715 |
Mounting position | vertical |
Operating / Storage temperature | -40 to +185 °F (-40 to +85 °C) |
Operating / Storage humidity | max. 95 %RH (non-condensing) |
Dimensions | 2.54 x 1.65 x 1.5" (64.5 x 42 x 38 mm) |
Weight | approx. 2 oz. (60 g) |
Protection type | IP20 |
1 When connecting with stranded wires, wire end ferrules must be used.
Part No. | Operating voltage | Setting range | Approvals | ||
---|---|---|---|---|---|
01131.2-00 | DC 12-48 V (min. DC 10 V, max. DC 60 V) | -20 to +60 °C | UL File No. E164102 | EAC | |
01131.2-01 | DC 12-48 V (min. DC 10 V, max. DC 60 V) | -4 to +140 °F | UL File No. E164102 | EAC |
Technical Drawing

- www.stego-usa.com>
- Products>
- Regulating>
- Regulators>
- ETL 011 | Electronic Thermostat (DC, low signals)